Call a Specialist Today! (02) 9388 1741
Free Delivery! Free Delivery!

APC Smart-UPS RT 3000VA RM 120V
APC Smart-UPS RT, 2100 Watts / 3000 VA,Input 120V / Output 120V, Interface Port DB-9 RS-232, Smart-Slot, Extended runtime model, Rack Height 3U

APC Smart-UPS RT 3000VA RM 120V

This product is not available for purchase in Australia. Please Contact Us for assistance with an appropriate solution.


A versatile UPS developed for the harshest power conditions in the world.

Smart-UPS On-Line provides high density, true double-conversion on-line power protection for servers, voice / data networks, medical labs, and light industrial applications. Capable of supporting loads from 1 to 20kVA in a rack/tower convertible form, the Smart-UPS On-Line is available from 2U to 12U. Recent family extensions at 15 and 20kVA enable support of power hungry blade servers or heavily loaded equipment racks. When business-critical systems require runtime in hours, not minutes, Smart-UPS On-Line can be configured with matching battery packs to comply with aggressive runtime demands. The included PowerChute management software provides unattended graceful shutdown of network operating systems. All models 5kVA and above include an integrated Network Management Card for remote management (optional on models below 5 kVA). The entire Smart-UPS On-Line family provides value to customers with demanding power environments, including very wide input voltage window, extremely tight output voltage regulation, frequency regulation, internal bypass, and input power factor correction.

APC Smart-UPS RT 3000VA RM 120V - Back View

Features & Benefits:

Availability
Automatic internal bypass Supplies utility power to the connected loads in the event of a UPS overload condition or fault.
Scalable runtime Allows additional run time to be quickly added as needed.
Intelligent battery management Maximizes battery performance, life, and reliability through intelligent, precision charging.
Hot-swappable batteries Ensures clean, uninterrupted power to protected equipment while batteries are being replaced
Automatic restart of loads after UPS shutdown Automatically starts up the connected equipment upon the return of utility power.
Temperature-compensated battery charging Prolongs battery life by regulating the charge voltage according to battery temperature.
Manageability
Network manageable Provides remote management of the UPS over the network.
InfraStruXure Manager compatible Enables centralized management via the APC InfraStruXure® Manager.
SmartSlot Customize UPS capabilities with management cards.
LED status indicators Quickly understand unit and power status with visual indicators.
Serial Connectivity Provides management of the UPS via a serial port.
Serviceability
User-replaceable batteries Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
Automatic self-test Periodic battery self-test ensures early detection of a battery that needs to be replaced.
Predictive failure notification Provides early-warning fault analysis ensuring proactive component replacement.
Disconnected battery notification Warns when a battery is not available to provide backup power.
Audible alarms Provides notification of changing utility power and UPS conditions.
Adaptability
Plug-and-Play external batteries Ensures clean, uninterrupted power to the loads when adding extra runtime to the UPS.
Rack/Tower convertible Protects the initial investment in the UPS when migrating from tower to rack-mount environment.
Flash-upgradeable firmware Install maintenance releases of firmware remotely using FTP.
Protection
Frequency and voltage regulation Gives higher application availability by correcting poor frequency and voltage conditions without using the battery.
Power conditioning Protects connected loads from surges, spikes, lightning, and other power disturbances.
Input power factor correction Minimizes installation costs by enabling the use of smaller generators and cabling.
Generator compatible Ensures clean, uninterrupted power to the loads in the event of an extended power outage.
Cold-start capable Provides temporary battery power when the utility power is out.
Resettable circuit breakers Easy recovery from overloads; no need to replace a fuse.
Safety-agency approved Ensures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment. UL, FCC, CE, C-Tick approvals.

Technical Specifications:

Output
Output Power Capacity 2100 Watts / 3000 VA
Max Configurable Power 2100 Watts / 3000 VA
Nominal Output Voltage 120V
Output Voltage Distortion Less than 3%
Output Frequency (sync to mains) 50/60 Hz +/- 3 Hz user adjustable +/- 0.1
Crest Factor 3 : 1
Waveform Type Sine wave
Output Connections NEMA 5-15R(6) NEMA 5-15R


NEMA 5-20R(2) NEMA 5-20R
Input
Bypass Internal Bypass (Automatic and Manual)
Nominal Input Voltage 120V
Input Frequency 50/60 Hz +/- 5 Hz (auto sensing)
Input Connections NEMA L5-30PNEMA L5-30P
Cord Length 10 feet (3.05 meters)
Input voltage range for main operations 90 - 150V
Batteries & Runtime
Battery Type Maintenance-free sealed Lead-Acid battery with suspended electrolyte: leakproof
Included Battery Modules 2
Typical recharge time 2.50 hour(s)
Replacement battery cartridge RBC44
RBC™ Quantity 1
Typical Backup Time at Half Load 33.9 minutes (1050 Watts)
Typical Backup Time at Full Load 14.1 minutes (2100 Watts)
Runtime Chart Smart-UPS RT
Extended Run Options APC Smart-UPS RT 3000VA RM 120V
Communications & Management
Interface Port(s) DB-9 RS-232, Smart-Slot, USB
Available SmartSlot™ Interface Quantity 1
Control panel LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : Overload and Bypass Indicators
Audible Alarm Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm
Emergency Power Off (EPO) Yes
Surge Protection and Filtering
Surge energy rating 480 Joules
Filtering Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Physical
Maximum Height 5.10 inches (130 mm)
Maximum Width 17.00 inches (432 mm)
Maximum Depth 26.00 inches (660 mm)
Net Weight 120.00 lbs. (54.55 kg)
Shipping Weight 140.00 lbs. (63.64 kg)
Shipping Height 13.68 inches (347 mm)
Shipping Width 23.73 inches (603 mm)
Shipping Depth 38.60 inches (980 mm)
Color Black
Units per Pallet 6.00
Rack Height 3U
Environmental
Operating Environment 32 - 104°F (0 - 40°C)
Operating Relative Humidity 0 - 95%
Operating Elevation 0-10000 feet (0-3000 meters)
Storage Temperature 5 - 113°F (-15 - 45°C)
Storage Relative Humidity 0 - 95%
Storage Elevation 0-50000 feet (0-15000 meters)
Audible noise at 1 meter from surface of unit 55.00 dBA
Online Thermal Dissipation 655.00 BTU/hr
Conformance
Regulatory Approvals CSA,FCC Part 15 Class A,UL 1778
Standard Warranty 2 years repair or replace

Pricing Notes:

Assembly Services
InfraStruXure® Assembly Services
#WASSEMUPS-3R-SB-00
Our Price: Request a Quote
Get a Quote
-->